The TRT high temperature water heater with EVI compressor has an outlet water temperature of 80°C and is the best choice for your special requirements. These units are energy efficient and environmentally friendly. An ideal replacement for traditional boilers.
Features:
1. Environmental safety
The electrical components and the water system are completely cut off to ensure water safety, no pollution to the atmosphere, no greenhouse effect, and it is the safest water heater
2. Wide adaptability to climate zones
The specially designed heat pump has better climate adaptability and the working temperature range is -25ºC to 43ºC.
3. Energy saving
A heat pump water heater is a high-efficiency transfer heating device powered by electricity. The operating cost is only 1/4 of the electric water heater and 1/3 of the gas water heater.
4. Automatic intelligent control system
Adopt intelligent computer automatic control system, no labor cost, simple and convenient operation, making the heat pump work safe and reliable. The modular unit designed control panel can control the more flexible heat pump package, with a user-friendly operating system interface for easy operation.
5. Advanced testing methods
The world-class enthalpy potential laboratory is used to test heat pumps. In addition to the basic test items, we also test heat pumps. Test our heat pump performance in a temperature environment of -30°C.
6. Widely used
Heat pumps are suitable for homes, schools, hospitals, shower centers, swimming pools, etc. and industrial uses such as electroplating, drying, etc.
Specifications:
Model |
|
LM/D-72(HC) |
LM/D-95(HC) |
LM/D-120(HC) |
Power Supply |
V |
380V~415V/50Hz/3ph |
Refrigerant |
|
R407C |
Heating Capacity(A24/W28) |
KW |
80.0 |
100.0 |
120.0 |
Input Power of Heating |
KW |
15.53 |
19.38 |
23.26 |
COP |
|
5.15 |
5.16 |
5.16 |
Cooling Capacity(A35/W28) |
KW |
52.0 |
65.0 |
78.0 |
Input Power of Cooling |
KW |
16.83 |
20.99 |
25.19 |
EER |
|
3.09 |
3.10 |
3.10 |
Rated Current |
A |
29.5 |
36.8 |
44.2 |
Max Current |
A |
41.3 |
51.5 |
61.8 |
Max Input Power |
KW |
21.7 |
27.1 |
32.6 |
Fan Motor Power |
W |
800 |
1150 |
1150 |
Fan Motor Quantity |
Piece |
2 |
2 |
2 |
Condenser |
|
Titanium Tube-in-shell Heat Exchanger |
Water Flow |
L/h |
27515 |
34394 |
41273 |
Water Pressure Drop |
Kpa |
≤45 |
≤48 |
≤50 |
Net Weight |
kg |
482 |
582 |
710 |
Gross Weight |
kg |
506 |
611 |
745 |
Noise |
db |
75 |
78 |
79 |
Waterproof Classification |
|
IPX4 |
Electric Shock Proof Grade |
|
I |
Pipe Size (Internal Thread) |
mm |
75 |
90 |
90 |
Dimension |
mm |
1850*1000*1950 |
2000*1100*2080 |
2200*1100*2080 |
Packing Dimension |
mm |
1940*1120*2180 |
2090*1200*2260 |
2290*1200*2260 |
Compressor Model/Quantity |
|
ZW54KWP*2 |
VR144KSE*2 |
ZW108KAE*3 |