Energy Efficiency Grade: | One |
---|---|
Heat Temperature: | 50-70°C |
Work Environment: | Common Heat Pump |
Heat Source: | Air-source |
Heating Type: | Multi-power Heat |
Application: | Villa Family, Sauna and Swimming Pool, Hotels, Factory Hospital, Student Apartments, Beauty Salons, Restaurants, Home |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
The hot water heat pump draws heat from the surrounding air, and then transfers the heat to the water tank to heat the water. Air source heat pumps can be used not only to heat hot water, but also to heat and cool houses.
The hot water heat pump can heat water to 30°C to 60°C. It consumes 70-80% less electricity than traditional electric water heaters, so the heat pump will save you a lot of electricity bills.
Function
1. Heating
2. Cooling
3. Hot water
Hot Water Heat Pumps Features:
1. Well-known brand scroll compressor
2. Stainless steel storage tank or enamel storage tank.
3. Efficient and environmentally friendly R134A or R417A refrigerant, no ozone depletion
4. Copper pipe with inner groove, higher efficiency
5. Intelligent control: with LCD display and digital remote control
6. Water temperature adjustment range: 25ºC-60ºC
7. Electronic expansion valve (EEV) is used for reliable and high-precision expansion
.Shell and tube or in-tube water heat exchanger, the maximum working water pressure is up to 3.2Mpa
8. Compact design, optional 80L / 200L / 300L
9. Low noise, will not disturb neighbors
10. Automatic sterilization to ensure water quality
11. Extremely compact structure, beautiful appearance, good detachability
OEM/ODM Service
1. Galvanized steel or 304 stainless steel cabinet is optional.
2. Grey, white, black and other color is optional.
3. Heating function, cooling function, and hot water function are optional.
4. OEM brand name is optional.
5. ODM cabinet is optional.
6. Other power supplies (110V, 60Hz) are optional.
Warranty:
1. CE, CB, RoHS, Conform to EN14511-2:2011 test standard, ISO9001, ISO14001.
2. 2 year warranty
Hot Water Heat Pumps Specifications:
Triple supply parameters Cooling, heating and hot water functions | |||||
Item | KCHR-8I/BP Side wind |
KCHR-13I/BP Side wind) |
KCHR-15I/BP Side wind |
KCHR-15II/BP (Out of the wind) |
|
Rated voltage | 220V~50Hz | 220V~50Hz | 220V~50Hz | 380V 3N~50Hz | |
Cooling and heating | Nominal cooling capacity |
7.8kW(2kW-9kW) | 13kW(3kW-15kW) | 14.5kW(4kW-16.5kW) | 14.5kW(4kW-16.5kW) |
Nominal cooling power consumption |
2.77KW | 4.6KW | 5.27KW | 5.27KW | |
Nominal cooling(COP) | 2.81 | 2.82 | 2.75 | 2.75 | |
IPLV | 4.11 | 4.13 | 4.02 | 4.02 | |
Nominal heating capacity | 8.4kW(2.5kW-9.6kW) | 14kW(3.5kW-16kW) | 17kW(4.3kW-18.5kW) | 17kW(2.5kW-18.5kW) | |
Nominal heating power consumption |
2.78KW | 4.5KW | 5.6KW | 5.6KW | |
Heating | Nominal heating capacity | 6.8KW | 10.5KW | 13KW | 13KW |
Nominal heating power consumption |
1.75KW | 2.65KW | 3.3KW | 3.3KW | |
Nominal heating(COP) | 3.88 | 3.96 | 3.93 | 3.93 | |
Maximum operating current | 20A | 33A | 41A | 21A | |
Maximum power consumption | 4KW | 6.6KW | 7.9KW | 7.9KW | |
Rated water flow | 1.34m²/h | 2.24m²/h | 2.5m²/h | 2.5m²/h | |
Refrigerant/charge volume | R410A/1750g | R410A/4000g | R410A/4000g | R410A/4800g | |
noise | ≤54dB(A) | ≤56dB(A) | ≤57dB(A) | ≤58dB(A) | |
Water resistance | ≤14kPa | ≤15kPa | ≤21kPa | ≤21kPa | |
Maximum working pressure on low pressure/high pressure side |
4.5Mpa/0.15Mpa | 4.5Mpa/0.15Mpa | 4.5Mpa/0.15Mpa | 4.5Mpa/0.15Mpa | |
Allowable working pressure on suction/exhaust side |
4.5Mpa/0.15Mpa | 4.5Mpa/0.15Mpa | 4.5Mpa/0.15Mpa | 4.5Mpa/0.15Mpa | |
Anti-shock level | I | I | I | I | |
waterproof level | IPX4 | IPX4 | IPX4 | IPX4 | |
Unit size (l× w × h) | 1030×410×865(mm) | 1030×410×1390(mm) | 1030×410×1390(mm) | 820×780×1700(mm) | |
(Cold and warm) Caliber of inlet and outlet |
DN25 | DN32 | DN32 | DN32 | |
(Hot water) Caliber | DN20 | DN25 | DN25 | DN25 | |
Application area | 60 | 100 | 110 | 110 | |
Nominal refrigeration conditions: ambient dry bulb 35ºC, outlet temperature 7ºC. Nominal heating conditions: ambient dry bulb 7ºC, ambient wet bulb 6ºC, outlet temperature 45ºC |
|||||
Nominal hot water production conditions: ambient dry bulb 20ºC, ambient wet bulb 15ºC, initial water temperature 15ºC, end water temperature 55ºC. |
Suppliers with verified business licenses